1 / Drainage and venting design
A sanitary stack serves eight branch intervals. Its total connected drainage fixture units fit the proposed diameter, but the load entering one branch interval exceeds that diameter's branch-interval limit. What is the correct design response?
- Average the overloaded interval with the seven lighter intervals
- Use only the building-sewer table to approve the stack
- Select a diameter that satisfies both the total-stack and single-branch-interval limits
- Approve the stack because its total load is within the limit
Show answer & explanation
Select a diameter that satisfies both the total-stack and single-branch-interval limits
For a stack with more than three branch intervals, Table 710.1(2) limits both the total stack load and the load into any one branch interval. Passing only the total-stack column is insufficient.
IPC 2021 Table 710.1(2)