01 / General requirements
A listed panelboard is supplied with a torque value for its terminals. Which installation practice satisfies the terminal tightening requirement?
- Use an approved means to achieve the indicated terminal torque
- Use a torque value selected only from conductor ampacity
- Apply the same torque used for the breaker handle
- Tighten until the conductor insulation deforms
Show answer & explanation
Use an approved means to achieve the indicated terminal torque
Achieve the tightening torque indicated on the equipment or in its installation instructions using an approved means. A calibrated torque tool is one such means; follow any applicable manufacturer instructions.
NEC 2023 110.14(D)